| Part No. : NLB10-200AMP | Alternate P/N : NLB10200AMP | Manufacturer : military specifications |
| Item Name: circuit breaker | NSN: 5925-00-261-6528 (5925002616528) | CAGE Code: 81349 |
If you require part number NLB10-200AMP from Military Specifications which is described as a Circuit Breaker component ASAP Logistic Solutions is your sourcing solution. On this page, you can request a quote on part number NLB10-200AMP which is listed under the Federal Supply Class . To ensure that you only procure the exact item you need to be sure to note that this particular product is listed with the NSN 5925002616528 and was produced under the CAGE Code 81349. To learn more about this listing or to simply initiate the purchasing process, complete and submit the RFQ form on this page for part NLB10-200AMP today Within 15 minutes of receiving and reviewing a completed request based on the information you provide a member of our staff will contact you to provide a tailored solution to your comparison needs.
| NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
|---|---|---|---|---|---|---|
| 5925-00-261-6528 Item PartTypeName: CIRCUIT BREAKER | 5925 | 002616528 | 0 | P | ||
| CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
| U | U | |||||
| Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
| 260-4743-000 | 2 | 1 | C |
| MRC | Criteria | Characteristic |
|---|---|---|
| AAQL | BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
| ADAQ | BODY LENGTH | 5.000 INCHES NOMINAL |
| ADAT | BODY WIDTH | 4.750 INCHES NOMINAL |
| ADAU | BODY HEIGHT | 4.625 INCHES NOMINAL |
| AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 3.625 INCHES NOMINAL |
| AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.687 INCHES NOMINAL |
| AEBV | UNTHREADED MOUNTING HOLE DIAMETER | 0.250 INCHES NOMINAL |
| AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 4.500 INCHES NOMINAL |
| AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.500 INCHES NOMINAL |
| AJEC | BOSS HEIGHT | 0.312 INCHES NOMINAL |
| AKPX | POLE QUANTITY | 3 |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 2 UNTHREADED HOLE |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 200.0 AMPERES AC AND 200.0 AMPERES DC ALL LOCATIONS |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 125.0 AC AND 125.0 DC ALL LOCATIONS |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 10000.0 AC AND 5000.0 DC ALL LOCATIONS |
| CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
| CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS AND TIME DELAY ALL LOCATIONS |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 138.0 ALL LOCATIONS |
| CPRQ | RESET METHOD | MANUAL |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 10.000 MINIMUM AT 200 PCT AND 180.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
| CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT |
| CRCF | TRIP RELEASE AMBIENT TEMP RATING | 50.0 DEG CELSIUS MAXIMUM ALL LOCATIONS |
| CWJK | CASE MATERIAL | PLASTIC |
| FREQ | FREQUENCY IN HERTZ | 400.0 ALL LOCATIONS |
| TEST | TEST DATA DOCUMENT | 81349-MIL-C-17588 SPECIFICATION INCLUDES ENGINEERING TYPE BULLETINS,BROCHURES,ETC.,THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT EXCLUDES COMMERCIAL CATALOGS,INDUSTRY DIRECTORIES,AND SIMILAR TRADE PUBLICATIONS,REFLECTI |
| TTQY | TERMINAL TYPE AND QUANTITY | 6 SCREW |
If you have more than one item, you can also send us your part number list (Spreadsheet) by uploading your list here.
Upload