| Part No. : 1605-779 | Alternate P/N : 1605779 | Manufacturer : westinghouse electric corp |
| Item Name: circuit breaker | NSN: 5925-00-779-7307 (5925007797307) | CAGE Code: 79500 |
| FSC: 5925 Circuit Breakers |
If you require part number 1605-779 from Westinghouse Electric Corp which is described as a Circuit Breaker component ASAP Logistic Solutions is your sourcing solution. On this page, you can request a quote on part number 1605-779 which is listed under the Federal Supply Class 5925 Circuit Breakers. To ensure that you only procure the exact item you need to be sure to note that this particular product is listed with the NSN 5925007797307 and was produced under the CAGE Code 79500. To learn more about this listing or to simply initiate the purchasing process, complete and submit the RFQ form on this page for part 1605-779 today Within 15 minutes of receiving and reviewing a completed request based on the information you provide a member of our staff will contact you to provide a tailored solution to your comparison needs.
| NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
|---|---|---|---|---|---|---|
| 5925-00-779-7307 Item PartTypeName: CIRCUIT BREAKER | 5925 | 007797307 | 0 | P | ||
| CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
| U | A | |||||
| Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
| EHD2090 | 2 | 2 | 3 |
| MRC | Criteria | Characteristic |
|---|---|---|
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 10000.0 AC AND 5000.0 DC ALL LOCATIONS |
| CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
| CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | DUSTPROOF AND GENERAL PURPOSE AND FUNGUS RESISTANT |
| FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
| ABXD | BUSHING LENGTH | 0.125 INCHES NOMINAL |
| ADAQ | BODY LENGTH | 6.000 INCHES NOMINAL |
| ADAT | BODY WIDTH | 2.750 INCHES NOMINAL |
| AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.375 INCHES NOMINAL |
| AEBV | UNTHREADED MOUNTING HOLE DIAMETER | 0.188 INCHES NOMINAL |
| AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 4.500 INCHES NOMINAL |
| AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 3.375 INCHES NOMINAL |
| AKPX | POLE QUANTITY | 2 |
| APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC AND 250.0 DC ALL LOCATIONS |
| CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| CPRQ | RESET METHOD | MANUAL |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 55.000 MINIMUM AT 200 PCT AND 120.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
| CRCF | TRIP RELEASE AMBIENT TEMP RATING | 40.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
| CTJS | UNPACKAGED UNIT WEIGHT | 3.000 POUNDS NOMINAL |
| CWJK | CASE MATERIAL | PLASTIC |
| TTQY | TERMINAL TYPE AND QUANTITY | 4 COMPRESSION |
| AAQL | BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
| AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 5.062 INCHES NOMINAL |
| AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 2 UNTHREADED HOLE |
| BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| BBRJ | SPECIAL HANDLING FEATURE | MAGNETIC |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 90.0 AMPERES AC AND 90.0 AMPERES DC ALL LOCATIONS |
If you have more than one item, you can also send us your part number list (Spreadsheet) by uploading your list here.